Voltage Drop Calculator for LT Cables (3-phase and 1-phase)

Check the voltage drop of a cable run in volts and percent, and see whether it meets your limit before you lay the cable.

Open the calculator →

Formula

ΔV = √3 × I × L × (R cosφ + X sinφ) / 1000  (3-phase)

ΔV = 2 × I × L × (R cosφ + X sinφ) / 1000  (1-phase)

I in A, L in m, R and X in Ω/km from the cable data sheet

Worked example

100 A, 150 m run, R = 0.32 Ω/km, X = 0.08 Ω/km (example values - take yours from the cable data sheet), power factor 0.85, 415 V

ΔV = 1.732 × 100 × 150 × (0.32×0.85 + 0.08×0.527) / 1000 = 8.16 V = 1.97 %

Where engineers use it

How to use

  1. Click Open the calculator. It runs free in your browser, on desktop or phone.
  2. Enter your values. Units and typical ranges are shown next to each input.
  3. Read the result and the step-by-step working, then print or add it to your Project BOQ.

Questions

What is an acceptable voltage drop?

It depends on the code and your design basis; many designs use limits of a few percent from source to load. The suite lets you enter your own limit.

Can I solve for the cable size instead?

Yes, the Cable Sizing guided check picks the smallest size that meets both current and voltage-drop limits.