Formula

At transformer LV terminals: ISC = IFL × 100 / Z%

At a downstream board: ISC = V / (√3 × Ztotal), Ztotal = source + transformer + cable impedance

Worked example

2000 kVA, 433 V, impedance 6.25 %, infinite source

IFL = 2,667 A; ISC = 2,667 × 100 / 6.25 = 42.7 kA