Cooling Tower Efficiency Calculator - Range, Approach, Effectiveness

Check how well a cooling tower is working from its water inlet, outlet and wet bulb temperatures, and find evaporation loss and make-up water.

Open the calculator →

Formula

Range = Tin − Tout; Approach = Tout − Twb

Effectiveness = Range / (Range + Approach) × 100

Evaporation loss (m³/h) = 0.00085 × 1.8 × circulation (m³/h) × Range (°C)

Worked example

Inlet 40 °C, outlet 32 °C, wet bulb 28 °C, circulation 1,000 m³/h

Range = 8 °C, Approach = 4 °C, Effectiveness = 66.7 %, Evaporation = 12.24 m³/h

Where engineers use it

How to use

  1. Click Open the calculator. It runs free in your browser, on desktop or phone.
  2. Enter your values. Units and typical ranges are shown next to each input.
  3. Read the result and the step-by-step working, then print or add it to your Project BOQ.