Estimate the air-conditioning load of a room, building or AHU in TR, with sensible, latent and fresh-air parts and the supply air quantity.

Open the calculator →

Formula

Q (kW) = ṁ × (h1 − h2), ṁ = air flow (m³/s) × 1.2 kg/m³

1 TR = 3.517 kW

Worked example

AHU 5 m³/s, air enthalpy 60 kJ/kg in and 40 kJ/kg off the coil (read from a psychrometric chart)

Q = 5 × 1.2 × (60 − 40) = 120 kW = 34.1 TR

Where engineers use it

How to use

  1. Click Open the calculator. It runs free in your browser, on desktop or phone.
  2. Enter your values. Units and typical ranges are shown next to each input.
  3. Read the result and the step-by-step working, then print or add it to your Project BOQ.

Questions

Is there a quick thumb-rule method?

Yes, the Civil suite has an HVAC tonnage estimate by occupancy, and the MEP suite covers full building services.